HKE 10

HKE 10 hygiene air conditioning compact unit

Integrated climate unit for operating rooms according to RR 1b

The compact Weiss HKE 10 hygiene air conditioning unit is designed for climate control of an operating room integrated into a container. In addition to controlling temperature, the unit also controls air humidity.

A climate that conforms to the climate control and hygienic requirements of DIN 1946, part 4 is maintained in the interior. In addition, the cooling capacity (maximum 22 kW) and heating capacity (maximum 24 kW) meet the required standards. A special mounting system with buffer elements minimises vibration and solid-borne sound transmission in the operating rooms.

Features

  • Low weight due to welded aluminium frame
  • Gas-proof welded temperature control space (ABC operation possible)
  • electromagnetic compatibility in accordance with VG 95374
  • vibration and impact-resistant in accordance with VG 95332
  • mounting system with buffer elements for minimizing vibration and solid-borne sound transmission
  • air distribution system with integrated particulate filters
  • Air distribution system with integrated HEPA filters
  • Regulated humidification and dehumidification of air in the room through integrated humidifier
  • optional NBC protection system
  • easy installation
  • service-friendly
  • easy operation

Scope of supply

  • full air conditioning system
  • mounting system
  • operating panel
  • hygienic outlet
  • lint screen
  • sand filter
ASK A QUICK QUESTION
Industrial Air Conditioning Units

Technical Specifications

  HKE-10
NATO Stock Number (NSN)* 4120-12-336-7481
Cooling capacity kW 22,0
Refrigerant R134a
Heating capacity kW 24,0
Humidification capacity kg/h 6
Air quantity Intake air m³/h
Condenser air m³/h
1200
2000
Room class Operating room class I, Type B per DIN 1946, part 4
Inside temperature min. °C
max. °C
22
30
Relative humidity min. % r.h.
max. % r.h.
25
60
Operational ambient temperature °C -32 ... +49
Sound pressure Airborne sound level dB (A)
External sound dB (A)
50
63
Air distribution system Hygienic air conditioning outlet in accordance with DIN 1946, part 4
Filter Sand filter
Outside air filter
Fine filter
Particulate filter
Colour RAL 6031, bronze-green
Quality class G4 in accord. with DIN EN 779
Quality class F7 in accord. with DIN EN 779
Quality class S in accord. with DIN 24 185
Material Walls
Frame
Galvanized sheet metal
Aluminium profiles
Paint RAL 1013, pearl white
Dimensions Height - mm
Width AC - mm
Depth - mm
1900
1910
750
Weight without NBC system - kg
with NBC system - kg
930
1025
Power supply 3/N/PE/~50 Hz/400 V/24 V DC
Connected load kVA 32
*only base device